Types R622E and R652E, 2-PSI Regulators are Underwriters Laboratories (UL) listed regulators designed for 2-PSI LP-Gas systems. They are installed downstream from a first-stage regulator to reduce an inlet pressure of 10 psig / 0,69 bar to a nominal 2 psig / 0,14 bar outlet pressure. The 2-PSI Regulators are designed for domestic applications that supply 2 psig / 0,14 bar LP-Gas to a line regulator located inside the building. These units have white closing caps for easy identification.
Order 10 for a full case.
Features:
- Improved Accuracy
- Superior Relief Performance
- Corrosion-Resistant Materials
- Inlet Screen
- Test Ports for Easy System Checks
- Positive Drainage
- 20-Year Recommended Replacement Life
- UL Listed
Specifications:
- 3/4" FNPT Inlet x 3/4" FNPT Outlet
- Body Designed for Backmount Installations
- Maximum Inlet Pressure: 10psig; Maximum Emergency Inlet Pressure: 15 psig
- Capacity: 1,500,000 BTU/hr
- Outlet Pressure Range: 1 to 2.2 psig; Set Point: 2 psig